Siemens – 3VL2710-1ME36-2KA0

3VL2 (50 ... 160 A) Siemens – 3VL2710-1ME36-2KA0
Qty
Circuit breaker VL160N standard breaking capacity Icu=55kA, 415V AC 3-pole, line protection Trip Unit ETU20, LSI In=100A, rated current IR=40…100A, overload protection, ISD=1.5 to 10xIR, II=11xIN short-circuit protection with screw terminals ETU communication-capable Undervoltage release 440…480 V AC without auxiliary/alarm switch
Customs tariff number85362090
Expected originDE
Weight2.400 kg