Catalog>Siemens>Energy (PTD)>7SJ>7SJ64 / 7SJ>Siemens – 7SJ6422-5EB92-3FD4 L0D

Siemens – 7SJ6422-5EB92-3FD4 L0D

7SJ Siemens – 7SJ6422-5EB92-3FD4 L0D
Qty
MULTIFUNCTION PROTECTIVE RELAY SYNCHRONIZATION (OPTIONAL) AND RESISTANCE TEMPERATURE DETECTOR INTERFACE, CASE 1/2 19", 20BI, 8BO, 2 POWER RELAYS, (4 CONTACTS) GRAPHIC DISPLAY, 1 WATCHDOG CONTACT PHASE CURRENT TRANSFORMER 1A SENSITIVE EARTH CURRENT TRANSF. SUPPLY VOLTAGE:DC 110V TO 250V, AC 115V TO 230V, TRIGG.LEVEL BINARY INPUT DC 88V FLUSH MOUNTING CASE, SCREW TERMINALS LANGUAGE ENGLISH, 50/60HZ, IEC/ANSI, REGION WORLD, (LANGUAGE CHANGEABLE) SYSTEM PORT (ON REAR OF DEVICE) PORT B MODBUS, RS485 DIGSI 4/MODEM PORT (ON REAR OF DEVICE) PORT C DIGSI 4, RS485 METERING: PEAK VALUES, AVERAGE METER, MIN/MAX-VALUES, FAULT RECORDING FUNCTIONALITY:TOC+DIRECT. TOC+ IEE+SENSITIVE DIR. GROUND FAULT PHASE OVERCURRENT (50/51): I>,I>>,IP,REVERSE INTERLOCKING, INDEPENDENT OF PHASE ROTATION, GROUND OVERCURRENT (50N/51N): IE>, IE>>, IEP, SENSITIVE DIRECTIONAL GROUND PROTECTION IEE (67N),IEE>,IEE>> GROUND VOLTAGE DISPLACEMENT(64) DIRECTIONAL TIME OVERCURRENT (67N/67N WITH 50N/51N), PHASE ROTATION (47), OVERLOAD PROTECT.W. 2 TIME CONSTANTS(49) TRIP CIRCUIT SUPERVISION (74TC) BREAKER FAILURE PROTECT. (50BF) COLD LOAD PICKUP, INRUSH BLOCKING, NEGAT. SYNCHRONIZATION